Refrigeration plant pictures: externalRefrigeration plant pictures: external
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
Refrigeration plant pictures: internalsRefrigeration plant pictures: internals
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
Refrigeration plant: PFDRefrigeration plant: PFD
PROCESS EQUIPMENT:
Flash Tank
Oil Separator
H t E h (# 1 & # 2) Heat Exchangers (# 1 & # 2)
Chiller
HP Receiver
Compressor
Float Cage Float Cage
Please note the Dehydrator is not a part of the package
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
Refrigeration plant: Flash TankRefrigeration plant: Flash Tank
EQUIPMENT FLASHTANK MANUFACTURER ROCKETINDUSTRIES
CRN# B9592.2 YEARBUILT 1974
BASISOFINFORMATION ATTACHEDDATASHEET*THISDOCUMENTISNOTMEANTTOREPLACETHEACTUALDATASHEET
SERVICE CONDENSATENONCORROSIVE CODE ASMEUW12(A)71
DESIGNCONDITIONS DESIGNTEMP 300 F
DESIGNPRESSURE 1080 PSIG OPERATINGPRESSURE 920 PSIG
MAXALLOW.PRESSURE 1080 PSIG HYDROTESTPRESSURE 1620 PSIG
MATERIAL SPECIFICATIONSMATERIALSPECIFICATIONS
SHELLMATERIAL A53‐B TENSILESTRENGTH 60000
HEADMATERIAL A516‐70 TENSILESTRENGTH 70000
SIZESIZE
THICKNESS 0.9338 IN CORRALLOW. 0.125 IN
SHELLDIAMETER 14OD IN OALENGTH 7FT‐1IN FT‐IN
CAPACITY 6.05 FT3 X‐RAY SPOT
JOINTS
SEAM SEAMLESS JOINT BUTT JOINT @ 85% EFFY
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
SEAM SEAMLESS JOINT BUTTJOINT@85%EFFY
Refrigeration plant: Oil SeparatorRefrigeration plant: Oil Separator
EQUIPMENT LOWTEMPSEPARATOR MANUFACTURER ROCKETINDUSTRIES
CRN# B9591.2 YEARBUILT 1974
BASISOFINFORMATION ATTACHEDDATASHEET*THISDOCUMENTISNOTMEANTTOREPLACETHEACTUALDATASHEET
SERVICE OIL&GASNONCORROSIVE CODE ASMEUW12(A)71
DESIGNCONDITIONS DESIGNTEMP 300 F
DESIGNPRESSURE 1080 PSIG OPERATINGPRESSURE 920 PSIG
MAXALLOW.PRESSURE 1080 PSIG HYDROTESTPRESSURE 1620 PSIG
MATERIALSPECIFICATIONS
SHELLMATERIAL A53‐B TENSILESTRENGTH 60000
HEADMATERIAL A516‐70 TENSILESTRENGTH 70000
SIZE
THICKNESS 0.938 IN CORRALLOW. 0.125 IN
SHELLDIAMETER 18OD IN OALENGTH N/A FT‐IN
CAPACITY N/A FT3 X‐RAY SPOT
JOINTS
SEAM SEAMLESS JOINT BUTTJOINT@85%EFFY
NOZZLES
DIAMETER 2 IN WALLTHICKNESS 0.343 IN
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
MATERIAL A53‐B FLANGERATING 600
Refrigeration plant: Heat Exchanger IRefrigeration plant: Heat Exchanger I
EQUIPMENT S&THEATEXCHANGER1 MANUFACTURERBROWNFINTUBEENGINEERINGLTD.
CRN# B9334.2 YEARBUILT 1974
BASISOFINFORMATION ATTACHEDDATASHEET*THISDOCUMENTISNOTMEANTTOREPLACETHEACTUALDATASHEET
SERVICESWEETNATGAS/SWEET
NATGASCODE ASMESECTVIIIUW12C
DESIGNCONDITIONS
DESIGNPRESSURE DESIGNTEMP
SHELL 1000 PSIG SHELL 650 F
TUBE 1000 PSIG TUBE 650 F
TESTPRESSURE 1500 PSIGOPERATINGPRESSURE
N/A PSIG
MATERIALSPECIFICATIONS
MATERIAL MANNSA53GRB TENSILESTRENGTH 60000
SIZE
SHELLTHICKNESS 0.337 INHEATINGSURFACEAREA
58 FT2
HEADTHICKNESS 1.75 IN TUBETHICKNESS 0.095 IN
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
DIAMETER 4(IPS) IN OALENGTH 21FT‐ 10.125IN FT‐IN
Refrigeration plant: Heat Exchanger IIRefrigeration plant: Heat Exchanger II
EQUIPMENT S&THEATEXCHANGER1 MANUFACTURERBROWNFINTUBEENGINEERINGLTD.
CRN# B9334.2 YEARBUILT 1974
*THIS DOCUMENT IS NOT MEANT TO REPLACE THE ACTUAL DATABASISOFINFORMATION ATTACHEDDATASHEET
*THISDOCUMENTISNOTMEANTTOREPLACETHEACTUALDATASHEET
SERVICESWEETNATGAS/SWEET
NATGASCODE ASMESECTVIIIUW12C
DESIGNCONDITIONS
DESIGNPRESSURE DESIGNTEMP
SHELL 1000 PSIG SHELL 650 F
TUBE 1000 PSIG TUBE 650 F
TESTPRESSURE 1500 PSIGOPERATINGPRESSURE
N/A PSIG
MATERIALSPECIFICATIONS
MATERIAL USSSA53GRB TENSILESTRENGTH 60000
SIZE
SHELLTHICKNESS 0.337 INHEATINGSURFACEAREA
58 FT2
HEADTHICKNESS 1.75 IN TUBETHICKNESS 0.095 IN
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
DIAMETER 4(IPS) IN OALENGTH 21FT‐ 10.125IN FT‐IN
Refrigeration plant: ChillerRefrigeration plant: Chiller
EQUIPMENT S&THEATEXCHANGER1 MANUFACTURERBROWNFINTUBEENGINEERING
LTD.
CRN# B9334.2 YEARBUILT 1974
BASIS OF INFORMATION ATTACHED DATA SHEET*THISDOCUMENTISNOTMEANTTOREPLACETHEACTUALDATA
BASISOFINFORMATION ATTACHEDDATASHEETSHEET
SERVICESWEETNATGAS/FREON
12CODE ASMESECTVIIIUW12C
DESIGNCONDITIONS
DESIGN PRESSURE DESIGN TEMPDESIGNPRESSURE DESIGNTEMP
SHELL 1000 PSIG SHELL 650 F
TUBE 1000 PSIG TUBE 650 F
TEST PRESSURE 1500 PSIGOPERATING
N/A PSIGTESTPRESSURE 1500 PSIGPRESSURE
N/A PSIG
MATERIALSPECIFICATIONS
MATERIAL USSSA53GRB TENSILESTRENGTH 60000
SIZE
HEATING SURFACESHELLTHICKNESS 0.337 IN
HEATINGSURFACEAREA
72 FT2
HEADTHICKNESS 1.75 IN TUBETHICKNESS 0.095 IN
( )
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
DIAMETER 4(IPS) IN OALENGTH 26FT‐ 10.125IN FT‐IN
Refrigeration plant: Float CageRefrigeration plant: Float Cage
EQUIPMENT FLOATCAGE MANUFACTURER ROCKETINDUSTRIES
CRN# B9619.2 YEARBUILT 1974
BASISOFINFORMATION ATTACHEDDATASHEET*THISDOCUMENTISNOTMEANTTOREPLACETHEACTUALDATASHEET
SERVICE GLYCOL/WATERCONDENSATE CODE ASMEUW12(B)71
DESIGNCONDITIONS DESIGNTEMP 300 F
DESIGNPRESSURE 1080 PSIG OPERATINGPRESSURE 920 PSIG
MAXALLOW.PRESSURE N/A PSIG HYDROTESTPRESSURE 1620 PSIG
MATERIAL SPECIFICATIONSMATERIALSPECIFICATIONS
SHELLMATERIAL A53‐B TENSILESTRENGTH 60000
HEADMATERIAL A234WPB TENSILESTRENGTH N/A
SIZESIZE
THICKNESS 0.237 IN CORRALLOW. NONE IN
SHELLDIAMETER 4 IN OALENGTH 26FT‐39/64IN FT‐IN
CAPACITY 0.21 FT3 X‐RAY SPOT
JOINTS
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
SEAM SEAMLESS JOINT BUTTJOINT@80%EFFY
Refrigeration plant: HP ReceiverRefrigeration plant: HP Receiver
EQUIPMENT LOWTEMPSEPARATOR MANUFACTURER ROCKETINDUSTRIES
CRN# B9591.2 YEARBUILT 1974
BASISOFINFORMATION ATTACHEDDATASHEET*THISDOCUMENTISNOTMEANTTOREPLACETHEACTUALDATASHEET
SERVICE OIL&GASNONCORROSIVE CODE ASMEUW12(A)71
DESIGNCONDITIONS DESIGNTEMP 300 F
DESIGNPRESSURE 1080 PSIG OPERATINGPRESSURE 920 PSIG
MAXALLOW.PRESSURE 1080 PSIG HYDROTESTPRESSURE 1620 PSIG
MATERIALSPECIFICATIONS
SHELLMATERIAL A53‐B TENSILESTRENGTH 60000
HEADMATERIAL A516‐70 TENSILESTRENGTH 70000
SIZE
THICKNESS 0.938 IN CORRALLOW. 0.125 IN
SHELLDIAMETER 18OD IN OALENGTH N/A FT‐IN
CAPACITY N/A FT3 X‐RAY SPOT
JOINTS
SEAM SEAMLESS JOINT BUTTJOINT@85%EFFY
NOZZLES
DIAMETER 2 IN WALLTHICKNESS 0.343 IN
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
MATERIAL A53‐B FLANGERATING 600
Refrigeration plant: CompressorRefrigeration plant: Compressor
Horsepower 50‐75
No.ofCylinders 8
CFM 184.7
Weight(lbs) 1115
Unauthorized distribution, & reproduction prohibited. Use of report implies acceptance of disclaimer at the end of the report.
Refrigeration plant: AttachmentsRefrigeration plant: Attachments
• Hydrostatic Pressure Test Report• Hydrostatic Pressure Test Report
• Ultrasonic Examination Form
• ABSA Certificate of Inspection Permit
• Original Data Sheets (basis of report)
• Fabrication Drawings (basis of report)
• PFD (basis of report)
DISCLAIMER: This report has been generated by VZFOX Canada Engineering as an combinedinformation package of technical data provided by Jaycor Resources & H2S Technologies Ltd. forthe purpose of information accessibility by the reader. VZFOX Canada Engineering does not takeany liability nor makes any guarantee for the correctness, accuracy, and completeness of thisreport. It is based on best effort and does not reflect ownership on VZFOX Canada Engineering inany way or form. No technical work was undertaken to produce this report and the informationcontained here in is free of responsibility to VZFOX Canada Engineering. Jaycor Resources, H2STechnologies and any other party or individual shall hold VZFOX Canada Engineering harmlessand free of responsibility in the event of dispute and in the court of law.